Frequency Scan–Based Mitigation Approach of Subsynchronous Control Interaction in Type-3 Wind Turbines

dc.contributor.authorAlatar, Farisen
dc.contributor.authorMehrizi-Sani, Alien
dc.contributor.departmentElectrical and Computer Engineeringen
dc.date.accessioned2021-08-09T16:55:02Zen
dc.date.available2021-08-09T16:55:02Zen
dc.date.issued2021-07-30en
dc.date.updated2021-08-06T15:19:27Zen
dc.description.abstractIntegration of wind energy resources into the grid creates several challenges for power system dynamics. More specifically, Type-3 wind turbines are susceptible to subsynchronous control interactions (SSCIs) when they become radially connected to a series-compensated transmission line. SSCIs can cause disruptions in power generation and can result in significant damage to wind farm (WF) components and equipment. This paper proposes an approach to mitigate SSCIs using an online frequency scan, with optimized phase angles of voltage harmonic injection to maintain steady-state operation, to modify the controllers or the operating conditions of the wind turbine. The proposed strategy is simulated in PSCAD/EMTDC software on the IEEE second benchmark model for subsynchronous resonance. Simulation results demonstrate the effectiveness of this strategy by ensuring oscillations do not grow.en
dc.description.versionPublished versionen
dc.format.mimetypeapplication/pdfen
dc.identifier.citationAlatar, F.; Mehrizi-Sani, A. Frequency Scan–Based Mitigation Approach of Subsynchronous Control Interaction in Type-3 Wind Turbines. Energies 2021, 14, 4626.en
dc.identifier.doihttps://doi.org/10.3390/en14154626en
dc.identifier.urihttp://hdl.handle.net/10919/104613en
dc.language.isoenen
dc.publisherMDPIen
dc.rightsCreative Commons Attribution 4.0 Internationalen
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/en
dc.subjectdoubly fed induction generatoren
dc.subjectpower system transientsen
dc.subjectsubsynchronous control interactionen
dc.subjectseries compensationen
dc.subjectwind farmsen
dc.titleFrequency Scan–Based Mitigation Approach of Subsynchronous Control Interaction in Type-3 Wind Turbinesen
dc.title.serialEnergiesen
dc.typeArticle - Refereeden
dc.type.dcmitypeTexten

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
energies-14-04626.pdf
Size:
1.43 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
Name:
license.txt
Size:
0 B
Format:
Item-specific license agreed upon to submission
Description: