Non-Contact Lap Splices in Dissimilar Concretes

Files
TR Number
Date
2015-09-14
Journal Title
Journal ISSN
Volume Title
Publisher
Virginia Tech
Abstract

Non-contact lap splices placed within a single concrete placement are often used and have been studied in previous research projects. However, non-contact lap splices used with each bar in a different concrete placement such that there is a cold joint between the bars, have not been investigated. This situation is found in the repair of adjacent box beam bridges and in the construction of inverted T-beam systems, among others. It is vital to understand whether the same mechanisms are present across a cold joint with two different types of concrete as are present in traditional non-contact lap splices.

In this research, eight T-beam specimens with non-contact lap splices were tested. The spacing between the bars, the splice bar blockout length, and presence of transverse bars were varied to study the effectiveness of the splices. The beams were tested in four point bending so that the splice region was under constant moment and the tension forces in the spliced bars were constant. End and midspan deflections were measured along with surface strain measurements at midspan and at the quarter span points, top and bottom. Gap openings were also measured at the ends of the blockouts.

The main conclusions found from this research are that beams containing non-contact lap splices were able to develop nominal capacity with the bar spacing less than or equal to 4 in. and the blockout between 17 and 20 in. long. Extending the blockouts and adding transverse bars underneath the splices did not add to the capacity.

Description
Keywords
non-contact lap splice, very high performance concrete (VHPC), adjacent box beam bridge repair, inverted T-beam bridge