Online Voltage Stability Monitoring and Control Using Limited Synchrophasor Measurements

dc.contributor.authorZhu, Ruoxien
dc.contributor.committeechairLiu, Chen-Chingen
dc.contributor.committeememberCenteno, Virgilio A.en
dc.contributor.committeememberDe La Ree, Jaimeen
dc.contributor.departmentElectrical and Computer Engineeringen
dc.date.accessioned2020-03-05T13:30:41Zen
dc.date.available2020-03-05T13:30:41Zen
dc.date.issued2019en
dc.description.abstractAs the scale and complexity of an interconnected power grid has increased significantly, power systems can be operated close to the verge of voltage instability. With the application of Phasor Measurement Units (PMUs), dispatchers are able to monitor long term voltage stability in a real time operational environment. This research addresses the critical issues by proposing three different methods. Voltage Stability Assessment Index (VSAI) is a Thévenin Equivalent (TE) based method considering voltage dynamic mechanisms. To extend the model from one load bus to a critical load center, Optimal Power Flow-Loading limit (OPF-LI) is developed to assess the voltage stability margin. To utilize limited available PMU measurements, State Calculator (SC) is included in the algorithm to approximate the dynamic states at the buses where PMU measurements are not available. The online voltage regulating method in terms of On-load Tap Changer (OLTC) control is also investigated. The methods proposed in this research have been validated with the test cases from the WECC 179 bus system.en
dc.description.abstractgeneralThis thesis proposed a hybrid solution of voltage stability monitoring and control in a power system. For the performance of motors, heaters or other loads in the power system, it is important that the customers are supplied with stable voltage. The variation of the voltage may cause damages to the load. Therefore, the methods in this thesis provides a feasible solution to monitor voltage stability of load centers in a power system. In addition, a novel approach for voltage control is proposed to prevent a voltage collapse of the system. The simulation results illustrate that the approach introduced in this thesis is promising for real time application.en
dc.description.degreeM.S.en
dc.format.mediumETDen
dc.identifier.urihttp://hdl.handle.net/10919/97197en
dc.language.isoen_USen
dc.publisherVirginia Techen
dc.rightsCreative Commons Attribution-NonCommercial-NoDerivatives 4.0 Internationalen
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/en
dc.subjectPMUen
dc.subjectVoltage stabilityen
dc.subjectOLTC controlen
dc.titleOnline Voltage Stability Monitoring and Control Using Limited Synchrophasor Measurementsen
dc.typeThesisen
thesis.degree.disciplinePoweren
thesis.degree.grantorVirginia Polytechnic Institute and State Universityen
thesis.degree.levelmastersen
thesis.degree.nameM.S.en

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Zhu_R_T_2019.pdf
Size:
884.75 KB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
Name:
license.txt
Size:
1.5 KB
Format:
Item-specific license agreed upon to submission
Description:

Collections